Hotline : 0986227171
Introduction of Function
Main Features:
*LED Indicators display Detailed Real-Time UPS Status and UPS fault.
*Advanced MCU microprocessor control technology, ensure long life reliability.
*Wide input voltage range, Zero transfer time.
*Excellent Protection against over voltage, over load, over current, over charge and so on.
*Input L and N lines reverse wiring detection, Auto start when AC back.
*DC start function, Input PFC revise function.
*Humanization bypass output can be adjustable.
*Smart RS232 communication with monitoring software.
*Intelligent slot available for AS-400 Dry contact and SNMP card Remote control.
*Strong antijamming capability.
*Available to work with generators.
*Lightning, surge, short circuit, Network/fax/modem surge protection.
Specification:
LCD MODEL | EX1K | |
LED MODEL | T1K | |
Capacity | VA/W | 1000VA700W/800W |
Input | Norminal Range | 110/115/120VAC or 220/230/240VAC |
Voltage range | 60-138VAC or 115-300VAC | |
Frenquency Range | 50Hz: 46 - 54 Hz; 60Hz: 56 - 64 Hz | |
Phase | Single phase with Ground | |
Power Factor | >=0.97 | |
Output | Voltage | 110/115/120*(1±2%)VAC or 220/230/240*(1±2%) VAC |
Frenquency Range | 50/60Hz(Adjustable) 50Hz AC Mode: Follow AC Mode (AC Range 46 - 54 Hz); Battery Mode: 50Hz (1±2%) 60Hz AC Mode: Follow AC Mode( AC Range 56 - 64 Hz); Battery Mode: 60Hz(1±2%) | |
Wave Form | Pure Sine Wave | |
Power Factor | 0.7/0.8 | |
Harmonic Distortion | ||
Overload Capacity | 110%-150% Maintain 30s then turn to bypass output, over 150% maintain 200ms | |
Current Crest Ratio | .3:1 | |
Connection | Versatile socket*2 | |
Effciency | To AC Mode | 85% |
To Battery Mode | 83% | |
Battery | Type | Selaed free mainternace lead acid battery |
Nominal DC voltage | 12V7AH*(2 or 3pcs) | |
Back-up time (full time) | >=6minutes | |
Battery | Genuine acqui Zlpower | |
Recharge time | 5 hours to 90% of capacity full discharge | |
Charge current(MAX) | 1A | |
Charge voltage | 27.4/4.1.1/±0.6V | |
Bypass | Automatic transfer | On over load and UPS failure |
Before UPS power-on | Defaul "ON" user adjustable to"YES" | |
Transfer time | 0ms, less than 4ms from inverter to bypass and vice versa | |
Indicator | LED/LCD Display | UPS status, Battery capacity, loading, fault code |
Audible Alarm | Bypass, On battery mode, Battery low, Overload, Fault | |
Acoustic noise | At 1 meter distance | <45db |
Communication | Intelligent RS232 serial port | Software support Windows family software, Linux, Sun network operating system, IBM Aix, Compaq True64, SGI IRIX, Free BSD, HP-UX and MAC |
SNMP (optional) | Remote control UPS through SNMP management and internet | |
USB (Optional) | Windows family software and Mac OS | |
Network Surge Protection | RJ45 I/O port available for network or FAX/Telephone line/Modem | |
Environmental | Operating Temperature | 0-40°C |
Operating Humidity | 20-90% (Non Condensing) | |
Weight | Net weight (kg) | 13.5 |
UPS Dimension | L*W*H (mm) | 370*145*220 |
Warranty | 2 years |