Capacity | 80 KVA / 80 KW | 160 KVA / 160 KW | 200 KVA / 200 KW | 400 KVA / 400 KW | ||||
Numbers of parallel module | 1~4 | 1~8 | 1~10 | 1~20 | ||||
Numbers of redundancy module | 0~3 | 0~7 | 0~9 | 0~19 | ||||
UPS power module | 20 KVA / 20 KW | |||||||
INPUT | ||||||||
Rated voltage | 380 V / 400 V / 415 Vac | |||||||
Voltage range |
277 ~ 520 Vac (70% < load ≤ 100%) | |||||||
Rated frequency | 50 / 60 Hz (auto-sense) | |||||||
Frequency range | 40 ~ 70 Hz | |||||||
Power factor | ≥ 0.99 | |||||||
Total harmonic distortion (THDI) | ≤ 3% | |||||||
Bypass voltage range | Rated output voltage - 40% ~ rated output voltage + 20% (settable via LCD) | |||||||
OUTPUT | ||||||||
Voltage | 380 V / 400 V / 415 Vac | |||||||
Voltage regulation | ± 1% | |||||||
Frequency | Synchronized with utility in mains mode; | |||||||
Power factor | 1.0 | |||||||
Waveform | Pure sine wave | |||||||
Crest factor | 3:1 | |||||||
Total harmonic distortion (THDV) | ≤ 1% (linear load); ≤ 5% (non-linear load) | |||||||
Transfer time | 0ms | |||||||
Inverter overload capability | 110% ~130%: transfer to bypass in 10 mins; | |||||||
Bypass overload capability | ≤ 150%: long time running | |||||||
BATTERIES | ||||||||
DC voltage | ± 240 Vdc (options: ± 192 Vdc / ± 204 Vdc / ± 216 Vdc / ± 228 Vdc) | |||||||
Inbuilt battery of standard model | 40×12 V / 9 Ah for each module | |||||||
Charging current | 1 ~ 30 A / 60 A (settable via LCD) | 1 ~ 60 A / 120 A (settable via LCD) | ||||||
SYSTEM | ||||||||
Efficiency | ≥ 94% | |||||||
Display panel | 5.7 Inches LCD touch screen | |||||||
Alarm | Battery mode, low battery, fans fault etc. | |||||||
EMI | EN62040-2 | |||||||
EMS | IEC61000-4-2 (ESD) | |||||||
IEC61000-4-3 (RS) | ||||||||
IEC61000-4-4 (EFT) | ||||||||
IEC61000-4-5 (Surge) | ||||||||
COMMUNICAITONS | ||||||||
RS232 / RS485 / USB / dry contacts (standard) | Supports Windows® 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10 | |||||||
SNMP (option) | Power management from SNMP manager and web browser | |||||||
OTHERS | ||||||||
Humidity | 0~95% RH @ 0~40℃ (non-condensing) | |||||||
Noise level | ≤ 60 dB | |||||||
Module dimensions (W×D×H) (mm) | 482×590×131 | |||||||
Module weight | 28 kg / power module, 27 kg / charger module, 7 kg / monitoring module | |||||||
UPS dimensions (W×D×H) (mm) | 600×1000×1600 | 600×1000×2000 | 1200×1000×2000 | |||||
UPS packaged dimensions (W×D×H) (mm) | 700×1070×1760 | 700×1070×2160 | 700×1070×2160(×2) | |||||
UPS Net/Gross weight (kg) | 225 / 245 | 290 / 310 | 280 / 300 | 560 / 600 | ||||
Input / output / bypass breaker | Yes | Yes | No | No |